CORC  > 清华大学
Mechanism and mitigation of multi-mode sub-synchronous resonance
Liu Shiyu ; Xie Xiaorong ; Zhang Donghui
2010-10-12 ; 2010-10-12
关键词Practical Theoretical or Mathematical/ eigenvalues and eigenfunctions genetic algorithms power system control power transmission simulated annealing/ multimode sub-synchronous resonance Shangdu Tuoketuo China transmission system Inmongolia fixed-series capacitor supplementary excitation damping control genetic algorithm simulated annealing algorithm eigen-analysis PSCAD-EMTDC-based simulation/ B8110C Power system control B8120 Power transmission, distribution and supply B0260 Optimisation techniques
中文摘要The Shangdu and Tuoketuo of Inmongolia in China transmission systems use relatively high compensation levels of fixed-series capacitors which results in sub-synchronous resonance (SSR). This issue is hard to correct because of the multiple unstable SSR modes. This paper presents a study of a specific Shangdu transmission system. The eigenvalues were analyzed to investigate the basic mechanism and the main causes of the multi-mode SSR. Supplementary excitation damping control was then used to solve the problem with optimal control parameters obtained using a genetic, simulated annealing algorithm. An eigen-analysis and PSCAD/EMTDC-based simulations verify the effectiveness of the damping control for mitigating the multi-mode SSR and its adaptability to various power systems and operating conditions.
语种中文
出版者Tsinghua University Press ; China
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/82855]  
专题清华大学
推荐引用方式
GB/T 7714
Liu Shiyu,Xie Xiaorong,Zhang Donghui. Mechanism and mitigation of multi-mode sub-synchronous resonance[J],2010, 2010.
APA Liu Shiyu,Xie Xiaorong,&Zhang Donghui.(2010).Mechanism and mitigation of multi-mode sub-synchronous resonance..
MLA Liu Shiyu,et al."Mechanism and mitigation of multi-mode sub-synchronous resonance".(2010).