Indoor/outdoor relationship of PM2.5 concentration in typical buildings with and without air cleaning in Beijing | |
Deng, Gaofeng1,2; Li, Zenghe1; Wang, Zhichao2; Gao, Jubao3; Xu, Zhaowei2; Li, Jiandong2; Wang, Zhiyong2 | |
刊名 | INDOOR AND BUILT ENVIRONMENT |
2017 | |
卷号 | 26期号:1页码:60-68 |
关键词 | Indoor air quality Particulate matter 2.5 Public building Residential home Ventilation systems Air cleaning unit Indoor to outdoor ratio |
ISSN号 | 1420-326X |
英文摘要 | Indoor and outdoor particulate matter 2.5 (PM2.5) concentrations were monitored in seven sampling sites: basketball stadium, hotel, shopping centre, research centre, commercial office, apartment building and villa, to determine the indoor and outdoor relationship of PM2.5 mass concentration in the central area of Beijing from February 2014 to March 2014. The influence of four types of ventilation systems on indoor to outdoor (I/O) ratio of PM2.5 concentration was evaluated. The measured results show that the mean I/O ratio of the seven locations was 0.36 when the outdoor PM2.5 concentration was more than 150 mu g/m(3), and 1.1 when the outdoor PM2.5 concentration was less than 100 mu g/m(3), which implies that people's activities could be the most likely factor rather than outdoor sources for elevated indoor PM2.5 levels. The average I/O ratio was 0.69 for public buildings and 0.94 for residential homes, which illustrates that indoor PM2.5 concentrations could be dominated by outdoor sources for residential homes. Approximately 90% of the outdoor particles were removed in public buildings equipped with fan-coil unit with air cleaning plus fresh air system. The results demonstrate the need to improve indoor air quality by using a proper ventilation system with air cleaning. |
WOS标题词 | Science & Technology ; Technology ; Life Sciences & Biomedicine |
类目[WOS] | Construction & Building Technology ; Engineering, Environmental ; Public, Environmental & Occupational Health |
研究领域[WOS] | Construction & Building Technology ; Engineering ; Public, Environmental & Occupational Health |
关键词[WOS] | PARTICULATE MATTER ; OUTDOOR AIR ; INDOOR AIR ; PARTICLE NUMBER ; HONG-KONG ; QUALITY ; CHINA ; POLLUTION ; HOMES ; EXPOSURE |
收录类别 | SCI |
语种 | 英语 |
WOS记录号 | WOS:000394085700006 |
内容类型 | 期刊论文 |
源URL | [http://ir.ipe.ac.cn/handle/122111/21961] |
专题 | 过程工程研究所_多相复杂系统国家重点实验室 |
作者单位 | 1.Beijing Univ Chem Technol, Sch Sci, Beijing, Peoples R China 2.China Acad Bldg Res, State Key Lab Bldg Safety & Environm, Beijing, Peoples R China 3.Chinese Acad Sci, Inst Proc Engn, State Key Lab Multiphase Complex Syst, Beijing, Peoples R China |
推荐引用方式 GB/T 7714 | Deng, Gaofeng,Li, Zenghe,Wang, Zhichao,et al. Indoor/outdoor relationship of PM2.5 concentration in typical buildings with and without air cleaning in Beijing[J]. INDOOR AND BUILT ENVIRONMENT,2017,26(1):60-68. |