Determination of trace levels of haloacetic acids and perchlorate in drinking water by ion chromatography with direct injection
Liu, YJ; Mou, SF
2003
会议名称15th International Ion Chromatography Symposium
会议日期SEP 29-OCT 02, 2002
会议地点BALTIMORE, MARYLAND
关键词water analysis haloacetic acids perchlorate acetic acids inorganic anions
英文摘要Disinfection by products of haloacetic acids and perchlorate pose significant health risks, even at low mug/l levels in drinking water. A new method for the simultaneous determination of nine haloacetic acids (HAAs) and perchlorate as well as some common anions in one run with ion chromatography was developed. The HAAs tested included mono-, di-, trichloroacetic acids, mono, di-, tribromoacetic acids, bromochloroacetic acid, dibromochloroacetic acid, and bromodichloroacetic acid. Two high-capacity anion-exchange columns, a carbonate-selective column and a hydroxide-selective hydrophilic one, were used for the investigation. With the carbonate-selective column, the nine HAAs as well as fluoride, chloride, nitrite, nitrate, phosphate and sulfate could be well separated and determined in one run. With the very hydrophilic column and a gradient elution of sodium hydroxide, methanol and deionized water, the nine HAAs, fluoride, chloride, nitrite, nitrate as well as perchlorate could be simultaneously determined in one run within 34 min. The detection limits for HAAs were between 1.11 and 9.32 mug/l For perchlorate, it was 0.60 mug/l. (C) 2003 Elsevier Science B.V. All rights reserved.
ISSN号0021-9673
内容类型会议论文
源URL[http://ir.rcees.ac.cn/handle/311016/24797]  
专题生态环境研究中心_环境化学与生态毒理学国家重点实验室
推荐引用方式
GB/T 7714
Liu, YJ,Mou, SF. Determination of trace levels of haloacetic acids and perchlorate in drinking water by ion chromatography with direct injection[C]. 见:15th International Ion Chromatography Symposium. BALTIMORE, MARYLAND. SEP 29-OCT 02, 2002.
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace